Development and application of an integrated indoor air quality audit to an international hotel building in Taiwan

Nae Wen Kuo, Hsin Chen Chiang, Che Ming Chiang

研究成果: 雜誌貢獻期刊論文同行評審

19 引文 斯高帕斯(Scopus)

摘要

Indoor air quality (IAQ) has begun to surface as an important issue that affects the comfort and health of people; however, there is little research concerned about the IAQ monitoring of hotels up to now. Hotels are designed to provide comfortable spaces for guests. However, most complaints related to uncomfortable thermal environment and inadequate indoor air quality appear. In addition, microbial pollution can affect the health of tourists such as the Legionnaire's disease and SARS problems. This study is aimed to establish the comprehensive IAQ audit approach for hotel buildings with portable equipments, and one five-star international hotel in Taiwan was selected to exam this integrated approach. Finally, four major problems are identified after the comprehensive IAQ audit. They are: (1) low room temperature (21.8°C), (2) insufficient air exchange rate (<1.5 h-1), (3) formaldehyde contamination (>0.02 ppm), and (4) the microbial pollution (total bacteria: 2,624-3,799 CFU/m3). The high level of formaldehyde may be due to the emission from the detergent and cleaning agents used for housekeeping.

原文英語
頁(從 - 到)139-147
頁數9
期刊Environmental Monitoring and Assessment
147
發行號1-3
DOIs
出版狀態已發佈 - 2008

ASJC Scopus subject areas

  • Environmental Science(all)
  • Pollution
  • Management, Monitoring, Policy and Law

指紋 深入研究「Development and application of an integrated indoor air quality audit to an international hotel building in Taiwan」主題。共同形成了獨特的指紋。

引用此