TY - JOUR
T1 - Characterizing the performance of alternative evaporative cooling pad media in thermal environmental control applications
AU - Liao, Chung Min
AU - Singh, Sher
AU - Wang, Tin Sen
N1 - Funding Information:
Funding for this work was sponsored by the Chung-Cheng Agricultural Science and
PY - 1998/10
Y1 - 1998/10
N2 - This paper outlines the test procedure and describes how the alternative pad performance is affected by pad thickness and pad materials in the thermal environmental control applications. Many experimental pads were tested including one made of nonwoven fabric perforated pad and one made of coir fiber material. A wind tunnel experiment was performed to obtain equations for heat and mass transfer coefficients for the evaporative process through various thickness of alternative pad media Heat and mass transfer coefficients are nondimensionalized and curve fitted to yield the working equations: (1) coir fiber pad: h(H)/h(M) =0.32ρC(a)C(Pa)Le(2/3)(Le(s)/Le)(1/4), and (2) nonwoven fabric pad: h(H)/h(M) = 1.89ρ(a)C(Pa)Le(2/3)(Le(s)/Le)(1/4); where h(H) is heat transfer coefficient, h(M) is mass transfer coefficient, ρ(a) is air density, C(pa) is specific heat of air, Le is Lewis number, and Le(s) is Lewis number at water temperature. A determination for cooling efficiency in a wind tunnel system is also developed to relate efficiency, face velocity, and static pressure drop across pads. For a 15 cm pad, static pressure drops across the perforated pad and cooling efficiencies varied from 48 to 108 Pa and 81.19 to 81.89%, while 60 to 130 Pa and 89.69 and 92.86% for coir fiber material pads respectively under operating air velocities of 2.0 to 3.0 m/s.
AB - This paper outlines the test procedure and describes how the alternative pad performance is affected by pad thickness and pad materials in the thermal environmental control applications. Many experimental pads were tested including one made of nonwoven fabric perforated pad and one made of coir fiber material. A wind tunnel experiment was performed to obtain equations for heat and mass transfer coefficients for the evaporative process through various thickness of alternative pad media Heat and mass transfer coefficients are nondimensionalized and curve fitted to yield the working equations: (1) coir fiber pad: h(H)/h(M) =0.32ρC(a)C(Pa)Le(2/3)(Le(s)/Le)(1/4), and (2) nonwoven fabric pad: h(H)/h(M) = 1.89ρ(a)C(Pa)Le(2/3)(Le(s)/Le)(1/4); where h(H) is heat transfer coefficient, h(M) is mass transfer coefficient, ρ(a) is air density, C(pa) is specific heat of air, Le is Lewis number, and Le(s) is Lewis number at water temperature. A determination for cooling efficiency in a wind tunnel system is also developed to relate efficiency, face velocity, and static pressure drop across pads. For a 15 cm pad, static pressure drops across the perforated pad and cooling efficiencies varied from 48 to 108 Pa and 81.19 to 81.89%, while 60 to 130 Pa and 89.69 and 92.86% for coir fiber material pads respectively under operating air velocities of 2.0 to 3.0 m/s.
KW - Evaporative cooling
KW - Heat/mass transfer
KW - Pad-fan
KW - Wind tunnel
UR - http://www.scopus.com/inward/record.url?scp=0032188981&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=0032188981&partnerID=8YFLogxK
U2 - 10.1080/10934529809376795
DO - 10.1080/10934529809376795
M3 - Article
AN - SCOPUS:0032188981
SN - 1093-4529
VL - 33
SP - 1391
EP - 1417
JO - Journal of Environmental Science and Health - Part A Toxic/Hazardous Substances and Environmental Engineering
JF - Journal of Environmental Science and Health - Part A Toxic/Hazardous Substances and Environmental Engineering
IS - 7
ER -